Loading…
Prediction of cooling-coil performance under condensing conditions
The possibility of predicting chilled-water cooling-coil performance under condensing conditions using dry-surface heat transfer correlations is examined. Experimentally determined wet-surface Nusselt number data are presented and compared with dry-surface data obtained from the same cooling coils....
Saved in:
Published in: | The International journal of heat and fluid flow 1993-12, Vol.14 (4), p.391-400 |
---|---|
Main Authors: | , |
Format: | Article |
Language: | English |
Subjects: | |
Citations: | Items that this one cites Items that cite this one |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | The possibility of predicting chilled-water cooling-coil performance under condensing conditions using dry-surface heat transfer correlations is examined. Experimentally determined wet-surface Nusselt number data are presented and compared with dry-surface data obtained from the same cooling coils. The wet-surface Nusselt numbers show considerable scatter; some of the results are higher than the corresponding dry-surface correlations, while others are lower. A sensitivity analysis is presented to illustrate that the wet-surface Nusselt numbers are very sensitive to the uncertainties in the measured inlet dew-point temperature and the measured heat transfer rate. It is demonstrated that the use of dry-surface Nusselt number correlations in a coil model result in wet-surface heat transfer predictions that are generally within 5 percent of the experimentally determined value. |
---|---|
ISSN: | 0142-727X 1879-2278 |
DOI: | 10.1016/0142-727X(93)90013-D |