Prediction of cooling-coil performance under condensing conditions

The possibility of predicting chilled-water cooling-coil performance under condensing conditions using dry-surface heat transfer correlations is examined. Experimentally determined wet-surface Nusselt number data are presented and compared with dry-surface data obtained from the same cooling coils....

Full description

Saved in:
Bibliographic Details
Published in:The International journal of heat and fluid flow 1993-12, Vol.14 (4), p.391-400
Main Authors: Mirth, D.R., Ramadhyani, S.
Format: Article
Language:English
Subjects:
Citations: Items that this one cites
Items that cite this one
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:The possibility of predicting chilled-water cooling-coil performance under condensing conditions using dry-surface heat transfer correlations is examined. Experimentally determined wet-surface Nusselt number data are presented and compared with dry-surface data obtained from the same cooling coils. The wet-surface Nusselt numbers show considerable scatter; some of the results are higher than the corresponding dry-surface correlations, while others are lower. A sensitivity analysis is presented to illustrate that the wet-surface Nusselt numbers are very sensitive to the uncertainties in the measured inlet dew-point temperature and the measured heat transfer rate. It is demonstrated that the use of dry-surface Nusselt number correlations in a coil model result in wet-surface heat transfer predictions that are generally within 5 percent of the experimentally determined value.