Loading…
Cool Storage Performance of Integrated Heat Pump System with Triple-Sleeve Energy Storage Exchanger
A new integrated heat pump system with triple-sleeve energy storage exchanger was proposed. Experimental system was designed and developed. The cool storage performance of integrated system was studied. The results showed that evaporating temperature was 1°C which was higher than ice storage. COP of...
Saved in:
Main Authors: | , , , |
---|---|
Format: | Conference Proceeding |
Language: | English |
Subjects: | |
Citations: | Items that this one cites Items that cite this one |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | A new integrated heat pump system with triple-sleeve energy storage exchanger was proposed. Experimental system was designed and developed. The cool storage performance of integrated system was studied. The results showed that evaporating temperature was 1°C which was higher than ice storage. COP of cool storage process at the highest point 2.4 dropped to 1.75. In general, system efficiency kept a high level. |
---|---|
ISSN: | 1876-6102 1876-6102 |
DOI: | 10.1016/j.egypro.2011.12.1185 |