Loading…

A robust islanding detection method with zero-non-detection zone for distribution systems with DG

•The proposed ID method has achieved Zero-NDZ with a reduced detection time.•The ID method meets the requirements established by the IEEE 929-2000 and 1547-2018 standards.•No DG power curtailment or signal injection is required to identify islanding.•The method exhibits high dependability, low cost...

Full description

Saved in:
Bibliographic Details
Published in:International journal of electrical power & energy systems 2021-12, Vol.133, p.107247, Article 107247
Main Authors: Serrano-Fontova, Alexandre, Martinez, Juan A., Casals-Torrens, Pau, Bosch, Ricard
Format: Article
Language:English
Subjects:
Citations: Items that this one cites
Items that cite this one
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:•The proposed ID method has achieved Zero-NDZ with a reduced detection time.•The ID method meets the requirements established by the IEEE 929-2000 and 1547-2018 standards.•No DG power curtailment or signal injection is required to identify islanding.•The method exhibits high dependability, low cost of implementation and a small degree of computational complexity. This paper proposes a strategy for detecting unintentional islanding operations (IOs) in distribution networks (DNs) with distributed generation (DG), which eliminating the non-detection zone (NDZ). This hybrid method achieves a zero-NDZ by taking advantage of both passive and active methodologies for an inverter-based DG scenario. The passive-based part of the proposed method considers settings with low thresholds and is activated whenever they are surpassed. The following step uses a three-phase static RC load. This load is connected to intentionally force the frequency and its derivative to exceed the established thresholds. Thus, the events with zero power imbalance can be identified. Unlike other existing methods, this technique does not degrade the power quality (PQ) and does not require DG output power curtailment. The evaluation of the proposed strategy has been carried out through an extensive set of scenarios considering both islanding and non-islanding events. The islanding detection capabilities of the proposed method have been explored considering a custom-made DN test system and the test system recommended by the IEEE 929-2000 standard. The proposed method has a simple implementation, requires a low level of computational complexity, provides a high degree of reliability, and assures fast islanding detection.
ISSN:0142-0615
1879-3517