Loading…
Containment testing of isolation rooms
Results from the tracer containment testing of four ‘state-of-the-art’ airborne infection isolation rooms, in a new hospital, are presented. A testing technician exited an isolation room several minutes after a small quantity of tracer gas was injected over the patient bed in that room. Easily measu...
Saved in:
Published in: | The Journal of hospital infection 2004-07, Vol.57 (3), p.228-232 |
---|---|
Main Authors: | , |
Format: | Article |
Language: | English |
Subjects: | |
Citations: | Items that this one cites Items that cite this one |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | Results from the tracer containment testing of four ‘state-of-the-art’ airborne infection isolation rooms, in a new hospital, are presented. A testing technician exited an isolation room several minutes after a small quantity of tracer gas was injected over the patient bed in that room. Easily measurable tracer gas concentrations were then found in the anterooms outside the patient rooms and corridor outside the isolation room suites. Containment factors for the isolation rooms and dilution factors in the anterooms and corridor were calculated, based on the measured tracer concentrations. These results indicate the desirability of evidence-based design standards and guidelines for assessing performance of airborne infection isolation rooms. The study also demonstrates that the tracer testing procedure yields comparable results for equivalent isolation room suites, suggesting good reproducibility of the testing method. |
---|---|
ISSN: | 0195-6701 1532-2939 |
DOI: | 10.1016/j.jhin.2004.01.032 |