Loading…

Robustness Analysis of Sensor Placement for Leak Detection and Location under Uncertain Operating Conditions

Some pressure sensor placement methods for leak detection and location in water distribution networks are based on the pressure sensitivity matrix analysis. This matrix depends on the network demands, which are nondeterministic, and the leak magnitudes, which are unknown. In this paper, the robustne...

Full description

Saved in:
Bibliographic Details
Main Authors: Blesa, J., Nejjari, F., Sarrate, R.
Format: Conference Proceeding
Language:English
Subjects:
Citations: Items that this one cites
Items that cite this one
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:Some pressure sensor placement methods for leak detection and location in water distribution networks are based on the pressure sensitivity matrix analysis. This matrix depends on the network demands, which are nondeterministic, and the leak magnitudes, which are unknown. In this paper, the robustness of a sensor placement methodology against the fault sensitivity matrix uncertainty is studied. The robustness study is illustrated by means of a small academic network as well as a district metered area in the Barcelona water distribution network. Results reveal that this uncertainty should be taken into account in the sensor placement methodology.
ISSN:1877-7058
1877-7058
DOI:10.1016/j.proeng.2014.11.453