Loading…
A new method for calibrating standard current transformers up to 20 kA
We have developed a method to obtain the ratio error and phase displacement of a single-stage current transformer (CT) by measuring four parameters in a CT equivalent circuit. The method was applied to CTs under test with a primary current in the range 10-20 000 A and a secondary current of 5 A. By...
Saved in:
Published in: | Measurement science & technology 2007-11, Vol.18 (11), p.3309-3315, Article 3309 |
---|---|
Main Authors: | , , , |
Format: | Article |
Language: | English |
Citations: | Items that this one cites Items that cite this one |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | We have developed a method to obtain the ratio error and phase displacement of a single-stage current transformer (CT) by measuring four parameters in a CT equivalent circuit. The method was applied to CTs under test with a primary current in the range 10-20 000 A and a secondary current of 5 A. By determining the errors of the CTs under test using this method, the ratio error and phase displacement of the standard CTs used as a reference in a CT test system could be obtained. This implies the establishment of a traceability chain of a national standard for CTs. The ratio error and phase displacement of the standard CTs obtained in this study are consistent with those measured at the Physikalisch-Technische Bundesanstalt in Germany using the same standard CTs within an expanded uncertainty (k = 2) in the overall primary current range investigated. |
---|---|
ISSN: | 0957-0233 1361-6501 |
DOI: | 10.1088/0957-0233/18/11/007 |