Breakdown Characteristic of N 2 -CO 2 Gas Mixtures under AC and DC Test Voltages
This study provides fundamental knowledge on the breakdown properties of N 2 -CO 2 gas mixture with a ratio of 20:80, 50:50, and 80:20. The gas mixtures were tested under HVAC and HVDC voltages with 1 bar (abs) pressure. The plane-plane and needle-plane electrodes were used with gap lengths between...
Saved in:
Published in: | Journal of physics. Conference series 2021-05, Vol.1874 (1), p.12027 |
---|---|
Main Authors: | , , , , |
Format: | Article |
Language: | English |
Citations: | Items that this one cites Items that cite this one |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | This study provides fundamental knowledge on the breakdown properties of N
2
-CO
2
gas mixture with a ratio of 20:80, 50:50, and 80:20. The gas mixtures were tested under HVAC and HVDC voltages with 1 bar (abs) pressure. The plane-plane and needle-plane electrodes were used with gap lengths between 0.5 cm to 2.5 cm. It is found that the breakdown voltage of N
2
-CO
2
mixture increased with the increased of CO
2
content. The breakdown voltage is also affected by the increment of gap distance for both electrode geometrics; plane-plane to represent the uniform field and needle-plane as the non-uniform field. The gas under uniform field configuration has a higher ability to withstand higher voltage levels compared under non-uniform field configuration. However, the non-uniform field provides a very high electric field intensity, which implies very high electric field stress. By increasing the percentage CO
2
in N
2
-CO
2
mixture, the insulation strength can reach about 64% that of pure SF
6
gas at the 0.1 MPa. |
---|---|