Loading…

Controlled closing on shunt reactor compensated transmission lines. I. Closing control device development

A control device for point-on-wave closing or autoreclosing of shunt reactor compensated transmission lines for the reduction of closing overvoltages is presented. The device is the first of its kind. It was put into field service successfully more than a year ago. Development aspects and basic inve...

Full description

Saved in:
Bibliographic Details
Published in:IEEE transactions on power delivery 1997-04, Vol.12 (2), p.734-740
Main Authors: Froehlich, K., Hoelzl, C., Stanek, M., Carvalho, A.C., Hofbauer, W., Hoegg, P., Avent, B.L., Peelo, D.F., Sawada, J.H.
Format: Article
Language:English
Subjects:
Citations: Items that this one cites
Items that cite this one
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:A control device for point-on-wave closing or autoreclosing of shunt reactor compensated transmission lines for the reduction of closing overvoltages is presented. The device is the first of its kind. It was put into field service successfully more than a year ago. Development aspects and basic investigations on the relevant transient switching phenomena are presented. The algorithm employed works independently of the shape of the voltage signal to be synchronized on by means of pattern recognition. Peculiarities of the hardware are high redundancy and a system to bypass the controller at any malfunction of the electronic circuits. The efficiency of the controller was verified by a combination of transient network analyser tests and EMTP simulations showing the ability of the device to suppress overvoltages. This procedure is generally recommended for future application of control devices as a type test procedure.
ISSN:0885-8977
1937-4208