Loading…

Controlled closing on shunt reactor compensated transmission lines. II. Application of closing control device for high-speed autoreclosing on BC Hydro 500 kV transmission line

In the past, BC Hydro used circuit breaker closing resistors to limit switching surges on its 500 kV transmission system. This approach was considered undesirable for new transmission lines and an innovative scheme incorporating special transmission line surge arresters and controlled high-speed aut...

Full description

Saved in:
Bibliographic Details
Published in:IEEE transactions on power delivery 1997-04, Vol.12 (2), p.741-746
Main Authors: Froehlich, K., Hoelzl, C., Stanek, M., Carvalho, A.C., Hofbauer, W., Hoegg, P., Avent, B.L., Peelo, D.F., Sawada, J.H.
Format: Article
Language:English
Subjects:
Citations: Items that this one cites
Items that cite this one
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:In the past, BC Hydro used circuit breaker closing resistors to limit switching surges on its 500 kV transmission system. This approach was considered undesirable for new transmission lines and an innovative scheme incorporating special transmission line surge arresters and controlled high-speed autoreclosing of the circuit breaker was developed. The scheme and its basis as applied on a new 330 km long 500 kV transmission line are described. Actual line switching tests, also described, confirmed the validity of the studies performed and applied design concepts, and the value of the scheme.
ISSN:0885-8977
1937-4208