Investigation of Corona and Field Effects of AC/DC Hybrid Transmission Lines
This paper describes laboratory and analytical studies that have been conducted by The Bonneville Power Administration to determine corona and electric field effects of a proposed ac/dc hybrid transmnission line. The proposed hybrid line would consist of a 500 kV ac circuit operating on the same str...
Saved in:
Published in: | IEEE transactions on power apparatus and systems 1981-01, Vol.PAS-100 (1), p.72-80 |
---|---|
Main Authors: | , , , |
Format: | Article |
Language: | English |
Subjects: | |
Citations: | Items that this one cites Items that cite this one |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | This paper describes laboratory and analytical studies that have been conducted by The Bonneville Power Administration to determine corona and electric field effects of a proposed ac/dc hybrid transmnission line. The proposed hybrid line would consist of a 500 kV ac circuit operating on the same structure as a ±500 kV dc circuit. Generally, the laboratory studies show that, with some modifications, equations used at BPA for calculating corona phenomenon can be used for a hybrid line. The paper also describes a technique for estimating dc electric field parameters which are enhanced by the presence of ions |
---|---|
ISSN: | 0018-9510 2995-6323 |
DOI: | 10.1109/TPAS.1981.316889 |