Loading…

An Assessment of the 5-mA 60-Hz Contact Current Safety Level

This paper is an investigation into the research basis of the 5-mA electrical safety standard. Although Dalziel's let-go current research is generally considered to be the basis of this standard, the 5-mA level actually predates Dalziel's investigations. Nevertheless, in spite of some limi...

Full description

Saved in:
Bibliographic Details
Published in:IEEE transactions on power apparatus and systems 1984-12, Vol.PAS-103 (12), p.3608-3614
Main Authors: Banks, Robert S., Vinh, Tieu
Format: Article
Language:English
Subjects:
Citations: Items that this one cites
Items that cite this one
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:This paper is an investigation into the research basis of the 5-mA electrical safety standard. Although Dalziel's let-go current research is generally considered to be the basis of this standard, the 5-mA level actually predates Dalziel's investigations. Nevertheless, in spite of some limitations in experimental design, Dalziel's let-go current experimental series is basically sound and well supports the 5-mA level as an occupational electrical safety standard. However, its applicability to the general population is questionable. Dalziel's data were developed from generally young, healthy subjects, and the standard's applicability to vulnerable populations such as children, the elderly, and the infirm is not known.
ISSN:0018-9510
2995-6323
DOI:10.1109/TPAS.1984.318413