Loading…
Performance Analysis of Closed loop Control of Diesel generator power supply for Base Transceiver (BTS) Load
This paper describes closed loop control of Diesel Generator (DG) supplying power to a Base Transceiver (BTS) load of a telecommunication tower, which is DC in nature. Detail modeling of Diesel Generator set has been presented.. The stability analysis of governor and excitation system has been carri...
Saved in:
Published in: | International journal of innovative technology and exploring engineering 2019-07, Vol.8 (9), p.2483-2495 |
---|---|
Main Authors: | , , |
Format: | Article |
Language: | English |
Citations: | Items that cite this one |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
cited_by | cdi_FETCH-LOGICAL-c2129-6117c11655c43c291f51bf1a8d0f002959f156678da3cf4e72a5300ac9bcf2613 |
---|---|
cites | |
container_end_page | 2495 |
container_issue | 9 |
container_start_page | 2483 |
container_title | International journal of innovative technology and exploring engineering |
container_volume | 8 |
creator | Siddiqui, Mohd. Khursheed Mallick, M.A. Iqbal, A. |
description | This paper describes closed loop control of Diesel Generator (DG) supplying power to a Base Transceiver (BTS) load of a telecommunication tower, which is DC in nature. Detail modeling of Diesel Generator set has been presented.. The stability analysis of governor and excitation system has been carried out in frequency domain. When DG source is connected to the BTS load bus through bridge rectifier, the output waveform distorted due to high odd harmonics content. To solve this problem a unity power factor rectifier has been designed. For the control operation of this UPFC rectifier, double loop mode control method has been used and results are presented. The complete system has been simulated in MATLAB-SIMULINK environment. |
doi_str_mv | 10.35940/ijitee.H7422.078919 |
format | article |
fullrecord | <record><control><sourceid>crossref</sourceid><recordid>TN_cdi_crossref_primary_10_35940_ijitee_H7422_078919</recordid><sourceformat>XML</sourceformat><sourcesystem>PC</sourcesystem><sourcerecordid>10_35940_ijitee_H7422_078919</sourcerecordid><originalsourceid>FETCH-LOGICAL-c2129-6117c11655c43c291f51bf1a8d0f002959f156678da3cf4e72a5300ac9bcf2613</originalsourceid><addsrcrecordid>eNpNkD1PwzAURS0EElXpP2DwCEOKnx3H8diGjyJVAokwR67zjFK5cWQXUP49pWVgulf3Smc4hFwDmwupc3bXbbs94nylcs7nTJUa9BmZcK7KTDAlz__1SzJLacsYA5FDWegJ8a8YXYg701uki974MXWJBkcrHxK21Icw0Cr0-xj873zfYUJPP7DHaPYh0iF8Y6Tpcxj8SA8kujQJaR1Nnyx2X4fvZlm_3dJ1MO0VuXDGJ5z95ZS8Pz7U1Spbvzw9V4t1ZjlwnRUAygIUUtpcWK7BSdg4MGXLHGNcS-1AFoUqWyOsy1FxIwVjxuqNdbwAMSX5iWtjSCmia4bY7UwcG2DNUVpzktYcpTUnaeIHTzdhfw</addsrcrecordid><sourcetype>Aggregation Database</sourcetype><iscdi>true</iscdi><recordtype>article</recordtype></control><display><type>article</type><title>Performance Analysis of Closed loop Control of Diesel generator power supply for Base Transceiver (BTS) Load</title><source>ROAD: Directory of Open Access Scholarly Resources</source><creator>Siddiqui, Mohd. Khursheed ; Mallick, M.A. ; Iqbal, A.</creator><creatorcontrib>Siddiqui, Mohd. Khursheed ; Mallick, M.A. ; Iqbal, A. ; Department of Electrical Engineering, Integral University, Lucknow, India ; Department of Electrical Engineering, Qatar University, Doha ; Associate Prof. in Electrical Engg. Dept in Integral University, Lucknow, India</creatorcontrib><description>This paper describes closed loop control of Diesel Generator (DG) supplying power to a Base Transceiver (BTS) load of a telecommunication tower, which is DC in nature. Detail modeling of Diesel Generator set has been presented.. The stability analysis of governor and excitation system has been carried out in frequency domain. When DG source is connected to the BTS load bus through bridge rectifier, the output waveform distorted due to high odd harmonics content. To solve this problem a unity power factor rectifier has been designed. For the control operation of this UPFC rectifier, double loop mode control method has been used and results are presented. The complete system has been simulated in MATLAB-SIMULINK environment.</description><identifier>ISSN: 2278-3075</identifier><identifier>EISSN: 2278-3075</identifier><identifier>DOI: 10.35940/ijitee.H7422.078919</identifier><language>eng</language><ispartof>International journal of innovative technology and exploring engineering, 2019-07, Vol.8 (9), p.2483-2495</ispartof><oa>free_for_read</oa><woscitedreferencessubscribed>false</woscitedreferencessubscribed><citedby>FETCH-LOGICAL-c2129-6117c11655c43c291f51bf1a8d0f002959f156678da3cf4e72a5300ac9bcf2613</citedby></display><links><openurl>$$Topenurl_article</openurl><openurlfulltext>$$Topenurlfull_article</openurlfulltext><thumbnail>$$Tsyndetics_thumb_exl</thumbnail><link.rule.ids>314,780,784,27924,27925</link.rule.ids></links><search><creatorcontrib>Siddiqui, Mohd. Khursheed</creatorcontrib><creatorcontrib>Mallick, M.A.</creatorcontrib><creatorcontrib>Iqbal, A.</creatorcontrib><creatorcontrib>Department of Electrical Engineering, Integral University, Lucknow, India</creatorcontrib><creatorcontrib>Department of Electrical Engineering, Qatar University, Doha</creatorcontrib><creatorcontrib>Associate Prof. in Electrical Engg. Dept in Integral University, Lucknow, India</creatorcontrib><title>Performance Analysis of Closed loop Control of Diesel generator power supply for Base Transceiver (BTS) Load</title><title>International journal of innovative technology and exploring engineering</title><description>This paper describes closed loop control of Diesel Generator (DG) supplying power to a Base Transceiver (BTS) load of a telecommunication tower, which is DC in nature. Detail modeling of Diesel Generator set has been presented.. The stability analysis of governor and excitation system has been carried out in frequency domain. When DG source is connected to the BTS load bus through bridge rectifier, the output waveform distorted due to high odd harmonics content. To solve this problem a unity power factor rectifier has been designed. For the control operation of this UPFC rectifier, double loop mode control method has been used and results are presented. The complete system has been simulated in MATLAB-SIMULINK environment.</description><issn>2278-3075</issn><issn>2278-3075</issn><fulltext>true</fulltext><rsrctype>article</rsrctype><creationdate>2019</creationdate><recordtype>article</recordtype><recordid>eNpNkD1PwzAURS0EElXpP2DwCEOKnx3H8diGjyJVAokwR67zjFK5cWQXUP49pWVgulf3Smc4hFwDmwupc3bXbbs94nylcs7nTJUa9BmZcK7KTDAlz__1SzJLacsYA5FDWegJ8a8YXYg701uki974MXWJBkcrHxK21Icw0Cr0-xj873zfYUJPP7DHaPYh0iF8Y6Tpcxj8SA8kujQJaR1Nnyx2X4fvZlm_3dJ1MO0VuXDGJ5z95ZS8Pz7U1Spbvzw9V4t1ZjlwnRUAygIUUtpcWK7BSdg4MGXLHGNcS-1AFoUqWyOsy1FxIwVjxuqNdbwAMSX5iWtjSCmia4bY7UwcG2DNUVpzktYcpTUnaeIHTzdhfw</recordid><startdate>20190730</startdate><enddate>20190730</enddate><creator>Siddiqui, Mohd. Khursheed</creator><creator>Mallick, M.A.</creator><creator>Iqbal, A.</creator><scope>AAYXX</scope><scope>CITATION</scope></search><sort><creationdate>20190730</creationdate><title>Performance Analysis of Closed loop Control of Diesel generator power supply for Base Transceiver (BTS) Load</title><author>Siddiqui, Mohd. Khursheed ; Mallick, M.A. ; Iqbal, A.</author></sort><facets><frbrtype>5</frbrtype><frbrgroupid>cdi_FETCH-LOGICAL-c2129-6117c11655c43c291f51bf1a8d0f002959f156678da3cf4e72a5300ac9bcf2613</frbrgroupid><rsrctype>articles</rsrctype><prefilter>articles</prefilter><language>eng</language><creationdate>2019</creationdate><toplevel>online_resources</toplevel><creatorcontrib>Siddiqui, Mohd. Khursheed</creatorcontrib><creatorcontrib>Mallick, M.A.</creatorcontrib><creatorcontrib>Iqbal, A.</creatorcontrib><creatorcontrib>Department of Electrical Engineering, Integral University, Lucknow, India</creatorcontrib><creatorcontrib>Department of Electrical Engineering, Qatar University, Doha</creatorcontrib><creatorcontrib>Associate Prof. in Electrical Engg. Dept in Integral University, Lucknow, India</creatorcontrib><collection>CrossRef</collection><jtitle>International journal of innovative technology and exploring engineering</jtitle></facets><delivery><delcategory>Remote Search Resource</delcategory><fulltext>fulltext</fulltext></delivery><addata><au>Siddiqui, Mohd. Khursheed</au><au>Mallick, M.A.</au><au>Iqbal, A.</au><aucorp>Department of Electrical Engineering, Integral University, Lucknow, India</aucorp><aucorp>Department of Electrical Engineering, Qatar University, Doha</aucorp><aucorp>Associate Prof. in Electrical Engg. Dept in Integral University, Lucknow, India</aucorp><format>journal</format><genre>article</genre><ristype>JOUR</ristype><atitle>Performance Analysis of Closed loop Control of Diesel generator power supply for Base Transceiver (BTS) Load</atitle><jtitle>International journal of innovative technology and exploring engineering</jtitle><date>2019-07-30</date><risdate>2019</risdate><volume>8</volume><issue>9</issue><spage>2483</spage><epage>2495</epage><pages>2483-2495</pages><issn>2278-3075</issn><eissn>2278-3075</eissn><abstract>This paper describes closed loop control of Diesel Generator (DG) supplying power to a Base Transceiver (BTS) load of a telecommunication tower, which is DC in nature. Detail modeling of Diesel Generator set has been presented.. The stability analysis of governor and excitation system has been carried out in frequency domain. When DG source is connected to the BTS load bus through bridge rectifier, the output waveform distorted due to high odd harmonics content. To solve this problem a unity power factor rectifier has been designed. For the control operation of this UPFC rectifier, double loop mode control method has been used and results are presented. The complete system has been simulated in MATLAB-SIMULINK environment.</abstract><doi>10.35940/ijitee.H7422.078919</doi><tpages>13</tpages><oa>free_for_read</oa></addata></record> |
fulltext | fulltext |
identifier | ISSN: 2278-3075 |
ispartof | International journal of innovative technology and exploring engineering, 2019-07, Vol.8 (9), p.2483-2495 |
issn | 2278-3075 2278-3075 |
language | eng |
recordid | cdi_crossref_primary_10_35940_ijitee_H7422_078919 |
source | ROAD: Directory of Open Access Scholarly Resources |
title | Performance Analysis of Closed loop Control of Diesel generator power supply for Base Transceiver (BTS) Load |
url | http://sfxeu10.hosted.exlibrisgroup.com/loughborough?ctx_ver=Z39.88-2004&ctx_enc=info:ofi/enc:UTF-8&ctx_tim=2024-12-30T20%3A45%3A23IST&url_ver=Z39.88-2004&url_ctx_fmt=infofi/fmt:kev:mtx:ctx&rfr_id=info:sid/primo.exlibrisgroup.com:primo3-Article-crossref&rft_val_fmt=info:ofi/fmt:kev:mtx:journal&rft.genre=article&rft.atitle=Performance%20Analysis%20of%20Closed%20loop%20Control%20of%20Diesel%20generator%20power%20supply%20for%20Base%20Transceiver%20(BTS)%20Load&rft.jtitle=International%20journal%20of%20innovative%20technology%20and%20exploring%20engineering&rft.au=Siddiqui,%20Mohd.%20Khursheed&rft.aucorp=Department%20of%20Electrical%20Engineering,%20Integral%20University,%20Lucknow,%20India&rft.date=2019-07-30&rft.volume=8&rft.issue=9&rft.spage=2483&rft.epage=2495&rft.pages=2483-2495&rft.issn=2278-3075&rft.eissn=2278-3075&rft_id=info:doi/10.35940/ijitee.H7422.078919&rft_dat=%3Ccrossref%3E10_35940_ijitee_H7422_078919%3C/crossref%3E%3Cgrp_id%3Ecdi_FETCH-LOGICAL-c2129-6117c11655c43c291f51bf1a8d0f002959f156678da3cf4e72a5300ac9bcf2613%3C/grp_id%3E%3Coa%3E%3C/oa%3E%3Curl%3E%3C/url%3E&rft_id=info:oai/&rft_id=info:pmid/&rfr_iscdi=true |