Simple Geomagnetic Induced Current Detection and Monitoring in Power Transformers
This paper presents a detection system of geomagnetic induced currents based on the measurement of the magnetic field outside the magnetic core; it is possible to evaluate the core operating conditions of power transformers under the effect of geomagnetic induced currents. The nonlinear behavior of...
Saved in:
Published in: | Measurement and control (London) 2016-09, Vol.49 (7), p.230-233 |
---|---|
Main Authors: | , , |
Format: | Article |
Language: | English |
Subjects: | |
Citations: | Items that this one cites Items that cite this one |
Online Access: | Request full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | This paper presents a detection system of geomagnetic induced currents based on the measurement of the magnetic field outside the magnetic core; it is possible to evaluate the core operating conditions of power transformers under the effect of geomagnetic induced currents. The nonlinear behavior of the core due to asymmetric saturation produces a distortion in the external magnetic field which can be evaluated by the measurement of the magnitude of even harmonics; we describe the experimental setup and the instrumentation required for real-time detection of asymmetric saturation caused by quasi-DC magnetic fields. The experimental results obtained by simulating the presence of geomagnetic induced currents are presented. |
---|---|