Loading…

Aspects regarding the use of recovered energy for air conditioning

In the paper the authors analyze the possibility of using the energy recovered from combustion gases, for air cooling. The objective is to evaluate the thermal potential of combustion gases from a cogeneration plant with a 3 MW electric power, located in Buzau. The monitoring data for the cogenerati...

Full description

Saved in:
Bibliographic Details
Published in:E3S web of conferences 2019-01, Vol.111, p.6013
Main Authors: Calotă, Răzvan, Girip, Alina, Istrate, Sergiu, Ilie, Anica, Nichita, Mădălina, Cublesan, Valentin
Format: Article
Language:English
Subjects:
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:In the paper the authors analyze the possibility of using the energy recovered from combustion gases, for air cooling. The objective is to evaluate the thermal potential of combustion gases from a cogeneration plant with a 3 MW electric power, located in Buzau. The monitoring data for the cogeneration system shows that the average flue gas temperature at the exit to the atmosphere is 125° C and the mass flow rate of the combustion gases is 18351 kg/h. The thermal potential of combustion gases isused for the preparation of hot water at 85°C for the operation of a LiBr-H 2 O solution absorption plant. Finally, the authors present a comparative study between the classic cooling system using chiller with mechanical vapor compression (VCM) and the absorption plant supplied by recovered energy from the cogeneration system, high lighting the advantage of the proposed trigeneration system.
ISSN:2267-1242
2555-0403
2267-1242
DOI:10.1051/e3sconf/201911106013