Flow Boiling Heat Transfer Performance Comparison of Skived Straight and CNC Diverging Microchannels Heat Sinks
SUMMARYFlow reversal and partial dryout are the most severe issue while applying flow boiling in microchannel heat sinks. Some studies have been conducted to resolve this flow reversal problem. One of the most promising design is the diverging channel. This study compared the flow boiling heat trans...
Saved in:
Main Authors: | , , , , , , |
---|---|
Format: | Conference Proceeding |
Language: | English |
Subjects: | |
Online Access: | Request full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | SUMMARYFlow reversal and partial dryout are the most severe issue while applying flow boiling in microchannel heat sinks. Some studies have been conducted to resolve this flow reversal problem. One of the most promising design is the diverging channel. This study compared the flow boiling heat transfer performance of refrigerant R-245fa in a 2-pass diverging microchannel heat sink and in a commercialized skived microchannel heat sink. The test results showed that the maximum thermal resistance of the skived straight channel heat sink are from 28% lower to 4.2% higher than that of diverging channel heat sink. The flow pressure drops in the skived channel heat sink are from 30% to 48% higher than those in diverging channel heat sink. |
---|---|
ISSN: | 2577-1000 |
DOI: | 10.23919/SEMI-THERM59981.2023.10267893 |