Investigating Replacements for Sulfur Hexafluoride in High Voltage Gas Switches
SF 6 has been the gas of choice in high-voltage spark gap switches due to its high dielectric strength, stable breakdown voltage, and low acute toxicity hazard; however, SF 6 is a greenhouse gas with a 100-year global warming potential (GWP) 23,500 times greater than CO 2 . Lower GWP alternatives ar...
Saved in:
Main Authors: | , , , , , , |
---|---|
Format: | Conference Proceeding |
Language: | English |
Subjects: | |
Online Access: | Request full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | SF 6 has been the gas of choice in high-voltage spark gap switches due to its high dielectric strength, stable breakdown voltage, and low acute toxicity hazard; however, SF 6 is a greenhouse gas with a 100-year global warming potential (GWP) 23,500 times greater than CO 2 . Lower GWP alternatives are desired to reduce the environmental impact of large pulsed-power systems such as the Z facility at Sandia National Laboratories. The fluoronitrile C4F7N and fluoroketone C 5 F 10 O (marketed as Novec™ 4710 and Novec™ 5110, respectively, by 3M™) have shown promise in mixtures with low overall GWP for on-grid SF 6 replacement. However, their suitability for repetitive switching applications has not been well explored. |
---|---|