Loading…

Five Years' Field Trials of Detuning Pendulums for Galloping Control

Field trials of detuning pendulums for controlling galloping of iced conductors have been in place on operating single and bundle conductor lines for five years and have generated considerable observational data. A technique of analysis has been developed which permits these observations of gallopin...

Full description

Saved in:
Bibliographic Details
Published in:IEEE transactions on power apparatus and systems 1984-02, Vol.PAS-103 (2), p.318-327
Main Authors: Havard, D. G., Pohlman, J. C.
Format: Article
Language:English
Subjects:
Citations: Items that this one cites
Items that cite this one
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:Field trials of detuning pendulums for controlling galloping of iced conductors have been in place on operating single and bundle conductor lines for five years and have generated considerable observational data. A technique of analysis has been developed which permits these observations of galloping on conductors with detuning pendulums to be compared with those on similar untreated conductors for a range of single conductor sizes in the data bank. For single conductors between 25 mm (1 inch) and 50 mm (2 inch) in diameter on spans between 100 m (300 ft) and 400 m (1200 ft) in length, properly applied detuning pendulums are demonstrated to provide effective control of galloping. For other sizes of single conductors and for bundle conductors additional observations are required to confirm the present promising indications.
ISSN:0018-9510