Loading…
Measurement of partial discharges at rapidly changing voltages
This work presents a measuring system for PDs at repetitive voltages with short rise times, based on a coupling device adapted for this kind of voltages and a method for removing contributions from the applied voltage. The potential of the system has been demonstrated through measurements of PDs aro...
Saved in:
Published in: | IEEE transactions on dielectrics and electrical insulation 2008-06, Vol.15 (3), p.823-831 |
---|---|
Main Authors: | , , , |
Format: | Article |
Language: | English |
Subjects: | |
Citations: | Items that this one cites Items that cite this one |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | This work presents a measuring system for PDs at repetitive voltages with short rise times, based on a coupling device adapted for this kind of voltages and a method for removing contributions from the applied voltage. The potential of the system has been demonstrated through measurements of PDs around a needle in air at voltages of 5.5 kV - 9.5 kV with rise times down to 10 mus. The observations obtained with this PD source prove that the measuring technique described enables detailed studies of PD properties under repetitive rapidly changing voltage waveforms in the investigated range of voltages and rise times. |
---|---|
ISSN: | 1070-9878 1558-4135 1558-4135 |
DOI: | 10.1109/TDEI.2008.4543120 |