Loading…
New PD measurement method for high power transformer PDM in service operation
Partial discharge measurement is a kind of effective condition check method for high power transformer. Normally, when a high power transformer needs to be checked by partial discharge measurement periodically, outage is required. Here, a newly developed measurement method for transformer is introdu...
Saved in:
Main Authors: | , , , |
---|---|
Format: | Conference Proceeding |
Language: | English |
Subjects: | |
Online Access: | Request full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | Partial discharge measurement is a kind of effective condition check method for high power transformer. Normally, when a high power transformer needs to be checked by partial discharge measurement periodically, outage is required. Here, a newly developed measurement method for transformer is introduced in which a new kind of capacitive coupling sensor is applied. The sensor consists of a pair of metal plates and a high frequency CT, which can be installed at the flange of the high voltage bushing of the transformer during the transformer in commercial service operation, without any outage. |
---|---|
DOI: | 10.1109/CMD.2008.4580436 |