Loading…
The effect research on transformers and protections under HVDC monopole ground operation mode
The neutral point potential of the grounding transformer will be changed when HVDC system operates in a dc monopole ground return mode and dc bias may be generated. Dc bias will change exciting currentdasias waveform. Then large quantity of even and odd harmonics will be produced. The harmonics will...
Saved in:
Main Authors: | , , , |
---|---|
Format: | Conference Proceeding |
Language: | English |
Subjects: | |
Online Access: | Request full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | The neutral point potential of the grounding transformer will be changed when HVDC system operates in a dc monopole ground return mode and dc bias may be generated. Dc bias will change exciting currentdasias waveform. Then large quantity of even and odd harmonics will be produced. The harmonics will do harm to the transformer and its protection. This paper uses PSCAD/EMTDC to create a simulation model. It emulates exciting current of a practical 750 kV single-phase transformer in variant cases under dc bias. It studies the distortion of exciting current, harmonic distribution, the peak value of the exciting current under dc bias. Meanwhile, the performance of transformer protection in this harmonic environment is analyzed. The loss made by exciting currentpsilas distortion and elevated temperature rise of core tie-plate are quantitative calculated. |
---|---|
DOI: | 10.1109/UPEC.2008.4651479 |