Power quality monitoring in distribution network using pseudomeasurement

This paper introduces a method to monitor power quality in a large 33 kV distribution network with minimal power quality recorders. This is achieved by using an intelligent driven application which is pseudo-measurement based, to approximate the bus voltages and currents at various busses in the net...

Full description

Saved in:
Bibliographic Details
Main Authors: Kanaesalingam, S.R.K., Ramachandaramurthy, V.K.
Format: Conference Proceeding
Language:English
Subjects:
Online Access:Request full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:This paper introduces a method to monitor power quality in a large 33 kV distribution network with minimal power quality recorders. This is achieved by using an intelligent driven application which is pseudo-measurement based, to approximate the bus voltages and currents at various busses in the network. Bus impedance matrix is manipulated by rewriting the node-voltage equations for an n-bus power system. This technique is further incorporated with a logic algorithm called adaptive linear algorithm (Adaline) to ensure the voltage and current has minimum deviation compared to the actual measurement at site. The technique developed in this paper can be utilized in power quality monitoring for a large area.
ISSN:2159-3442
2159-3450
DOI:10.1109/TENCON.2009.5396052