Numerical Simulation and Experimental Investigation of NaSCN-NH3 Diffusion Absorption Refrigeration System
As a new absorption refrigeration system, NaSCN-NH 3 diffusion absorption refrigeration system uses a solution of an inorganic salt compound as the absorbent, ammonia as the refrigerant. This paper presents some parameters that affecting on the performance of NaSCN-NH 3 diffusion absorption refriger...
Saved in:
Main Authors: | , , , |
---|---|
Format: | Conference Proceeding |
Language: | English |
Subjects: | |
Online Access: | Request full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | As a new absorption refrigeration system, NaSCN-NH 3 diffusion absorption refrigeration system uses a solution of an inorganic salt compound as the absorbent, ammonia as the refrigerant. This paper presents some parameters that affecting on the performance of NaSCN-NH 3 diffusion absorption refrigeration system. By comparing simulation and experimental data, the results show that the COP of NaSCN-NH 3 diffusion absorption refrigeration device set to 2 kW cooling capacity can reach 0.4, when the regeneration temperature is 80°C~105°C, the concentration is 0.38~0.5 and condensation temperature is 30°C. |
---|---|