Loading…

Interruption ability of a self extinguishing type gas circuit breaker

Interruption ability of a self-extinguishing-type gas circuit breaker has been investigated while varying several structural factors. With a thermal puffer cylinder (0.7 l volume), excellent interruption ability (9.5 to 31.5 kA at 84 kV) was obtained for the condition of a breaker-terminal fault (BT...

Full description

Saved in:
Bibliographic Details
Published in:IEEE transactions on power delivery 1990-07, Vol.5 (3), p.1362-1369
Main Authors: Arita, H., Natsui, K., Tsukushi, M., Kurosawa, Y., Hirasawa, K.
Format: Article
Language:English
Subjects:
Citations: Items that this one cites
Items that cite this one
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:Interruption ability of a self-extinguishing-type gas circuit breaker has been investigated while varying several structural factors. With a thermal puffer cylinder (0.7 l volume), excellent interruption ability (9.5 to 31.5 kA at 84 kV) was obtained for the condition of a breaker-terminal fault (BTF). In the condition of a short-line fault (SLF), however, its interruptible arcing time width at the same current levels was only 0.2 to 0.3 cycles, where 0.5 cycles was proposed. The critical current, which is the minimum current which the breaker can interrupt, was several kiloamperes.< >
ISSN:0885-8977
1937-4208
DOI:10.1109/61.57978