Interruption ability of a self extinguishing type gas circuit breaker
Interruption ability of a self-extinguishing-type gas circuit breaker has been investigated while varying several structural factors. With a thermal puffer cylinder (0.7 l volume), excellent interruption ability (9.5 to 31.5 kA at 84 kV) was obtained for the condition of a breaker-terminal fault (BT...
Saved in:
Published in: | IEEE transactions on power delivery 1990-07, Vol.5 (3), p.1362-1369 |
---|---|
Main Authors: | , , , , |
Format: | Article |
Language: | English |
Subjects: | |
Citations: | Items that this one cites Items that cite this one |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | Interruption ability of a self-extinguishing-type gas circuit breaker has been investigated while varying several structural factors. With a thermal puffer cylinder (0.7 l volume), excellent interruption ability (9.5 to 31.5 kA at 84 kV) was obtained for the condition of a breaker-terminal fault (BTF). In the condition of a short-line fault (SLF), however, its interruptible arcing time width at the same current levels was only 0.2 to 0.3 cycles, where 0.5 cycles was proposed. The critical current, which is the minimum current which the breaker can interrupt, was several kiloamperes.< > |
---|---|
ISSN: | 0885-8977 1937-4208 |
DOI: | 10.1109/61.57978 |