Loading…

Protection Scheme Using SFCL for Electric Railways With Automatic Power Changeover Switch System

In this paper, we propose a protection scheme using a superconducting fault current limiter (SFCL) for the electric railway with traction power supply system with the automatic power changeover switch (ACS) system. The Korean electric railway uses a Scott transformer with many traction power substat...

Full description

Saved in:
Bibliographic Details
Published in:IEEE transactions on applied superconductivity 2012-06, Vol.22 (3), p.5600604-5600604
Main Authors: SHIN, Hee-Sang, CHO, Sung-Min, KIM, Jae-Chul
Format: Article
Language:English
Subjects:
Citations: Items that this one cites
Items that cite this one
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:In this paper, we propose a protection scheme using a superconducting fault current limiter (SFCL) for the electric railway with traction power supply system with the automatic power changeover switch (ACS) system. The Korean electric railway uses a Scott transformer with many traction power substations. Each traction power substation has a neutral section. The ACS system is being installed at the neutral section and studied. In this system, shorting between the M- and T-phases prevents phase-to-phase faults, which was not considered for the conventional AC railway, due to the ACS. The proposed protection scheme using the SFCL mitigates this problem. In addition, we analysed the effect of the proposed protection scheme using the time-domain transient simulation software PSCAD/EMTDC.
ISSN:1051-8223
1558-2515
DOI:10.1109/TASC.2011.2174812