Loading…
Reliability Assessment of Anti-surge Control System in Centrifugal Compressor
As a crucial part of the control system of a centrifugal compressor, it is very important to assure the reliability and practicability of anti-surge control system. In this paper, the mechanism of compressor surge is introduced, and the features are analyzed. In order to test the Safety Integrity Le...
Saved in:
Main Authors: | , , , , |
---|---|
Format: | Conference Proceeding |
Language: | English |
Subjects: | |
Online Access: | Request full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | As a crucial part of the control system of a centrifugal compressor, it is very important to assure the reliability and practicability of anti-surge control system. In this paper, the mechanism of compressor surge is introduced, and the features are analyzed. In order to test the Safety Integrity Level (SIL) of the compressor surge control system in a gas station, the Layer of Protection Analysis (LOPA) method is used for determining the needed SIL, and a quantitative analysis method-Fault Tree Analysis (FTA) is used to verify the SIL of the safety instrument system. Corresponding measures are proposed according to the assessment result. |
---|---|