Loading…
Diffusion coefficient in transformer pressboard insulation part 1: non impregnated pressboard
Water is harmful for transformers; the dynamic behavior of moisture influences the dielectric integrity and insulation aging in a transformer on operation. In this paper, the determination of the diffusion coefficient of moisture in transformer pressboard is tackled. This work has been focused in an...
Saved in:
Published in: | IEEE transactions on dielectrics and electrical insulation 2014-02, Vol.21 (1), p.360-368 |
---|---|
Main Authors: | , , , |
Format: | Article |
Language: | English |
Subjects: | |
Citations: | Items that this one cites Items that cite this one |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | Water is harmful for transformers; the dynamic behavior of moisture influences the dielectric integrity and insulation aging in a transformer on operation. In this paper, the determination of the diffusion coefficient of moisture in transformer pressboard is tackled. This work has been focused in analyzing non oil-impregnated pressboard, so the obtained coefficient is useful for studying the processes of transformer drying in factory. Drying experiments were developed in a thermogravimetric analyzer on nonimpregnated samples of pressboard subjected to different drying temperatures. The experimental conditions were simulated by means of a diffusion model implemented by means of Finite Element Method. The comparison between estimated and measured values allows drawing conclusions about the accuracy of the proposed coefficient. |
---|---|
ISSN: | 1070-9878 1558-4135 |
DOI: | 10.1109/TDEI.2013.004051 |