Design of new control strategies for a four-leg three-phase inverter to eliminate the neutral current under unbalanced loads

This paper presents new control strategies for a four-leg three-phase UPS inverter which is used in AC power distribution system in data centers. The IT loads are distributed between the three phase terminals and the neutral terminal of the inverter. Due to the natural unbalance of the three-phase l...

Full description

Saved in:
Bibliographic Details
Main Authors: Zhao-Qin Guo, Panda, Sanjib Kumar, Prasanna, I. V.
Format: Conference Proceeding
Language:English
Subjects:
Online Access:Request full text
Tags: Add Tag
No Tags, Be the first to tag this record!
cited_by
cites
container_end_page 1585
container_issue
container_start_page 1580
container_title
container_volume
creator Zhao-Qin Guo
Panda, Sanjib Kumar
Prasanna, I. V.
description This paper presents new control strategies for a four-leg three-phase UPS inverter which is used in AC power distribution system in data centers. The IT loads are distributed between the three phase terminals and the neutral terminal of the inverter. Due to the natural unbalance of the three-phase loads in the data center system, there exists a non-zero neutral current if the output voltage of the inverter is controlled to be three-phase balanced. The objective of this work is to eliminate the neutral current such that the thermal losses in the neutral conductor can be reduced and the power usage efficiency (PUE) in date centers can be improved. The elimination of the neutral current is achieved by controlling the inverter output voltages. Three different control methods are designed to dynamically adjust the amplitudes and the mutual phase differences of the three phase voltages, respectively. The effectiveness of the proposed strategies is validated through intensive simulations.
doi_str_mv 10.1109/IPEC.2014.6869795
format conference_proceeding
fullrecord <record><control><sourceid>ieee_CHZPO</sourceid><recordid>TN_cdi_ieee_primary_6869795</recordid><sourceformat>XML</sourceformat><sourcesystem>PC</sourcesystem><ieee_id>6869795</ieee_id><sourcerecordid>6869795</sourcerecordid><originalsourceid>FETCH-LOGICAL-i175t-4acafcaf48828dc6d4cab38be7c7d4a4abd567b898f4dab7f268c988f99ef96b3</originalsourceid><addsrcrecordid>eNotkMFKAzEYhCMoWGofQLzkBbYmu9lNcpRatVDQg57Lv8mfNrLNliSrCD68AQvDzGXmOwwht5wtOWf6fvO2Xi1rxsWyU52Wur0gCy0VF1LrWrKWXZJZzVtWdUyqa7JI6ZMx1tSsaet2Rn4fMfl9oKOjAb-pGUOO40BTjpBx7zFRN0YKxadYDbin-RARq9MBElIfvjBmjDSPFAd_9KGMSgMLayqEgZopRgyZTsGW2hR6GCAYtHQYwaYbcuVgSLg455x8PK3fVy_V9vV5s3rYVp7LNlcCDLgioVStrOmsMNA3qkdppBUgoLdtJ3ullRMWeunqThmtlNMane76Zk7u_rkeEXen6I8Qf3bnv5o_Zm5ijQ</addsrcrecordid><sourcetype>Publisher</sourcetype><iscdi>true</iscdi><recordtype>conference_proceeding</recordtype></control><display><type>conference_proceeding</type><title>Design of new control strategies for a four-leg three-phase inverter to eliminate the neutral current under unbalanced loads</title><source>IEEE Xplore All Conference Series</source><creator>Zhao-Qin Guo ; Panda, Sanjib Kumar ; Prasanna, I. V.</creator><creatorcontrib>Zhao-Qin Guo ; Panda, Sanjib Kumar ; Prasanna, I. V.</creatorcontrib><description>This paper presents new control strategies for a four-leg three-phase UPS inverter which is used in AC power distribution system in data centers. The IT loads are distributed between the three phase terminals and the neutral terminal of the inverter. Due to the natural unbalance of the three-phase loads in the data center system, there exists a non-zero neutral current if the output voltage of the inverter is controlled to be three-phase balanced. The objective of this work is to eliminate the neutral current such that the thermal losses in the neutral conductor can be reduced and the power usage efficiency (PUE) in date centers can be improved. The elimination of the neutral current is achieved by controlling the inverter output voltages. Three different control methods are designed to dynamically adjust the amplitudes and the mutual phase differences of the three phase voltages, respectively. The effectiveness of the proposed strategies is validated through intensive simulations.</description><identifier>ISSN: 2150-6078</identifier><identifier>EISBN: 9781479927050</identifier><identifier>EISBN: 1479927058</identifier><identifier>DOI: 10.1109/IPEC.2014.6869795</identifier><language>eng</language><publisher>IEEE</publisher><subject>Data center system ; Inverters ; Neutral current ; Simulation ; Unbalanced loads ; Uninterruptible power systems</subject><ispartof>2014 International Power Electronics Conference (IPEC-Hiroshima 2014 - ECCE ASIA), 2014, p.1580-1585</ispartof><woscitedreferencessubscribed>false</woscitedreferencessubscribed></display><links><openurl>$$Topenurl_article</openurl><openurlfulltext>$$Topenurlfull_article</openurlfulltext><thumbnail>$$Tsyndetics_thumb_exl</thumbnail><linktohtml>$$Uhttps://ieeexplore.ieee.org/document/6869795$$EHTML$$P50$$Gieee$$H</linktohtml><link.rule.ids>309,310,780,784,789,790,27925,54555,54932</link.rule.ids><linktorsrc>$$Uhttps://ieeexplore.ieee.org/document/6869795$$EView_record_in_IEEE$$FView_record_in_$$GIEEE</linktorsrc></links><search><creatorcontrib>Zhao-Qin Guo</creatorcontrib><creatorcontrib>Panda, Sanjib Kumar</creatorcontrib><creatorcontrib>Prasanna, I. V.</creatorcontrib><title>Design of new control strategies for a four-leg three-phase inverter to eliminate the neutral current under unbalanced loads</title><title>2014 International Power Electronics Conference (IPEC-Hiroshima 2014 - ECCE ASIA)</title><addtitle>IPEC</addtitle><description>This paper presents new control strategies for a four-leg three-phase UPS inverter which is used in AC power distribution system in data centers. The IT loads are distributed between the three phase terminals and the neutral terminal of the inverter. Due to the natural unbalance of the three-phase loads in the data center system, there exists a non-zero neutral current if the output voltage of the inverter is controlled to be three-phase balanced. The objective of this work is to eliminate the neutral current such that the thermal losses in the neutral conductor can be reduced and the power usage efficiency (PUE) in date centers can be improved. The elimination of the neutral current is achieved by controlling the inverter output voltages. Three different control methods are designed to dynamically adjust the amplitudes and the mutual phase differences of the three phase voltages, respectively. The effectiveness of the proposed strategies is validated through intensive simulations.</description><subject>Data center system</subject><subject>Inverters</subject><subject>Neutral current</subject><subject>Simulation</subject><subject>Unbalanced loads</subject><subject>Uninterruptible power systems</subject><issn>2150-6078</issn><isbn>9781479927050</isbn><isbn>1479927058</isbn><fulltext>true</fulltext><rsrctype>conference_proceeding</rsrctype><creationdate>2014</creationdate><recordtype>conference_proceeding</recordtype><sourceid>6IE</sourceid><recordid>eNotkMFKAzEYhCMoWGofQLzkBbYmu9lNcpRatVDQg57Lv8mfNrLNliSrCD68AQvDzGXmOwwht5wtOWf6fvO2Xi1rxsWyU52Wur0gCy0VF1LrWrKWXZJZzVtWdUyqa7JI6ZMx1tSsaet2Rn4fMfl9oKOjAb-pGUOO40BTjpBx7zFRN0YKxadYDbin-RARq9MBElIfvjBmjDSPFAd_9KGMSgMLayqEgZopRgyZTsGW2hR6GCAYtHQYwaYbcuVgSLg455x8PK3fVy_V9vV5s3rYVp7LNlcCDLgioVStrOmsMNA3qkdppBUgoLdtJ3ullRMWeunqThmtlNMane76Zk7u_rkeEXen6I8Qf3bnv5o_Zm5ijQ</recordid><startdate>201405</startdate><enddate>201405</enddate><creator>Zhao-Qin Guo</creator><creator>Panda, Sanjib Kumar</creator><creator>Prasanna, I. V.</creator><general>IEEE</general><scope>6IE</scope><scope>6IL</scope><scope>CBEJK</scope><scope>RIE</scope><scope>RIL</scope></search><sort><creationdate>201405</creationdate><title>Design of new control strategies for a four-leg three-phase inverter to eliminate the neutral current under unbalanced loads</title><author>Zhao-Qin Guo ; Panda, Sanjib Kumar ; Prasanna, I. V.</author></sort><facets><frbrtype>5</frbrtype><frbrgroupid>cdi_FETCH-LOGICAL-i175t-4acafcaf48828dc6d4cab38be7c7d4a4abd567b898f4dab7f268c988f99ef96b3</frbrgroupid><rsrctype>conference_proceedings</rsrctype><prefilter>conference_proceedings</prefilter><language>eng</language><creationdate>2014</creationdate><topic>Data center system</topic><topic>Inverters</topic><topic>Neutral current</topic><topic>Simulation</topic><topic>Unbalanced loads</topic><topic>Uninterruptible power systems</topic><toplevel>online_resources</toplevel><creatorcontrib>Zhao-Qin Guo</creatorcontrib><creatorcontrib>Panda, Sanjib Kumar</creatorcontrib><creatorcontrib>Prasanna, I. V.</creatorcontrib><collection>IEEE Electronic Library (IEL) Conference Proceedings</collection><collection>IEEE Proceedings Order Plan All Online (POP All Online) 1998-present by volume</collection><collection>IEEE Xplore All Conference Proceedings</collection><collection>IEEE Electronic Library (IEL)</collection><collection>IEEE Proceedings Order Plans (POP All) 1998-Present</collection></facets><delivery><delcategory>Remote Search Resource</delcategory><fulltext>fulltext_linktorsrc</fulltext></delivery><addata><au>Zhao-Qin Guo</au><au>Panda, Sanjib Kumar</au><au>Prasanna, I. V.</au><format>book</format><genre>proceeding</genre><ristype>CONF</ristype><atitle>Design of new control strategies for a four-leg three-phase inverter to eliminate the neutral current under unbalanced loads</atitle><btitle>2014 International Power Electronics Conference (IPEC-Hiroshima 2014 - ECCE ASIA)</btitle><stitle>IPEC</stitle><date>2014-05</date><risdate>2014</risdate><spage>1580</spage><epage>1585</epage><pages>1580-1585</pages><issn>2150-6078</issn><eisbn>9781479927050</eisbn><eisbn>1479927058</eisbn><abstract>This paper presents new control strategies for a four-leg three-phase UPS inverter which is used in AC power distribution system in data centers. The IT loads are distributed between the three phase terminals and the neutral terminal of the inverter. Due to the natural unbalance of the three-phase loads in the data center system, there exists a non-zero neutral current if the output voltage of the inverter is controlled to be three-phase balanced. The objective of this work is to eliminate the neutral current such that the thermal losses in the neutral conductor can be reduced and the power usage efficiency (PUE) in date centers can be improved. The elimination of the neutral current is achieved by controlling the inverter output voltages. Three different control methods are designed to dynamically adjust the amplitudes and the mutual phase differences of the three phase voltages, respectively. The effectiveness of the proposed strategies is validated through intensive simulations.</abstract><pub>IEEE</pub><doi>10.1109/IPEC.2014.6869795</doi><tpages>6</tpages></addata></record>
fulltext fulltext_linktorsrc
identifier ISSN: 2150-6078
ispartof 2014 International Power Electronics Conference (IPEC-Hiroshima 2014 - ECCE ASIA), 2014, p.1580-1585
issn 2150-6078
language eng
recordid cdi_ieee_primary_6869795
source IEEE Xplore All Conference Series
subjects Data center system
Inverters
Neutral current
Simulation
Unbalanced loads
Uninterruptible power systems
title Design of new control strategies for a four-leg three-phase inverter to eliminate the neutral current under unbalanced loads
url http://sfxeu10.hosted.exlibrisgroup.com/loughborough?ctx_ver=Z39.88-2004&ctx_enc=info:ofi/enc:UTF-8&ctx_tim=2025-01-07T16%3A35%3A38IST&url_ver=Z39.88-2004&url_ctx_fmt=infofi/fmt:kev:mtx:ctx&rfr_id=info:sid/primo.exlibrisgroup.com:primo3-Article-ieee_CHZPO&rft_val_fmt=info:ofi/fmt:kev:mtx:book&rft.genre=proceeding&rft.atitle=Design%20of%20new%20control%20strategies%20for%20a%20four-leg%20three-phase%20inverter%20to%20eliminate%20the%20neutral%20current%20under%20unbalanced%20loads&rft.btitle=2014%20International%20Power%20Electronics%20Conference%20(IPEC-Hiroshima%202014%20-%20ECCE%20ASIA)&rft.au=Zhao-Qin%20Guo&rft.date=2014-05&rft.spage=1580&rft.epage=1585&rft.pages=1580-1585&rft.issn=2150-6078&rft_id=info:doi/10.1109/IPEC.2014.6869795&rft.eisbn=9781479927050&rft.eisbn_list=1479927058&rft_dat=%3Cieee_CHZPO%3E6869795%3C/ieee_CHZPO%3E%3Cgrp_id%3Ecdi_FETCH-LOGICAL-i175t-4acafcaf48828dc6d4cab38be7c7d4a4abd567b898f4dab7f268c988f99ef96b3%3C/grp_id%3E%3Coa%3E%3C/oa%3E%3Curl%3E%3C/url%3E&rft_id=info:oai/&rft_id=info:pmid/&rft_ieee_id=6869795&rfr_iscdi=true