Design of LCL filter for improving robustness of grid-connected voltage source inverter
In this paper, a design method of the LCL filter for the robustness of grid-connected voltage source inverter (VSI) is proposed in the case of the grid-side current feedback control. A stable region is investigated for the robust operation of VSI with regard to stability margins without a passive or...
Saved in:
Main Authors: | , , , , |
---|---|
Format: | Conference Proceeding |
Language: | English |
Subjects: | |
Online Access: | Request full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | In this paper, a design method of the LCL filter for the robustness of grid-connected voltage source inverter (VSI) is proposed in the case of the grid-side current feedback control. A stable region is investigated for the robust operation of VSI with regard to stability margins without a passive or an active damping. The proposed design method presents a means to place the resonance frequency in a proposed stable region, and considers the harmonic currents injected into the grid. Also, the grid impedance is considered for the system stability. The inverter-side inductance and the filter capacitance performs an important role in the proposed design method. A grid-connected VSI with filter parameters designed by the proposed design method is experimentally verified. |
---|---|
ISSN: | 2329-3721 2329-3748 |
DOI: | 10.1109/ECCE.2014.6953798 |