Fuzzy space vector modulation-based control of modified instantaneous powers in active filter
A simple SVM-based fuzzy control is presented in the paper. The outputs of the fuzzy controller represent the switching schemes of the voltage-type inverter and lengths of the time intervals composing the switching period. The errors in instantaneous active and reactive powers, which should be gener...
Saved in:
Main Author: | |
---|---|
Format: | Conference Proceeding |
Language: | English |
Subjects: | |
Online Access: | Request full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | A simple SVM-based fuzzy control is presented in the paper. The outputs of the fuzzy controller represent the switching schemes of the voltage-type inverter and lengths of the time intervals composing the switching period. The errors in instantaneous active and reactive powers, which should be generated to compensate high harmonics of a nonlinear load, are the input variables of the fuzzy control of an inverter-based active filter. In order to keep phase currents sinusoidal also in case of unsymmetrical voltage system, a modification of reference average powers is suggested. The control algorithm has been verified by a simulation. |
---|---|