Adaptive 100% Injection-Based Generator Stator Ground Fault Protection With Real-Time Fault Location Capability
The paper presents a novel adaptive stator ground fault protection scheme with fault location capability for high-impedance grounded synchronous generators. The protection scheme uses already available neutral grounding signals in the existing subharmonic injection protection to obtain a Kalman adap...
Saved in:
Published in: | IEEE transactions on power delivery 2018-10, Vol.33 (5), p.2364-2372 |
---|---|
Main Authors: | , , , |
Format: | Article |
Language: | English |
Subjects: | |
Citations: | Items that this one cites Items that cite this one |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | The paper presents a novel adaptive stator ground fault protection scheme with fault location capability for high-impedance grounded synchronous generators. The protection scheme uses already available neutral grounding signals in the existing subharmonic injection protection to obtain a Kalman adaptive filter (KAF) for real-time stator insulation parameter estimation. The KAF estimator yields a method of continuous tracking of stator insulation condition during healthy operations. This information is then used for real-time stator ground fault detection as well as fault location. The effectiveness of the proposed method is verified using extensive experiments performed on a lab-scale unit-connected generating station. |
---|---|