Reproduction of a High Impedance Double line-to-ground Fault Using Real Oscillography Data

This paper presents the reproduction of an actual high impedance fault (HIF) event of type double line-to-ground using real oscillography data and ATP-EMTP software. The event occured in an overhead distribution system connected to substation Salinópolis 13.8 kV, after two cabes broke and touched a...

Full description

Saved in:
Bibliographic Details
Main Authors: Heringer, W. R., Cordeiro, M. A. M., Paye, J. C. H., Sousa, A. L., Leao, A. P., Vieira, J. P. A., Santos, M. C., Cardoso, G., de Morais, A. P., Wontroba, A., Farias, P. E.
Format: Conference Proceeding
Language:English
Subjects:
Online Access:Request full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:This paper presents the reproduction of an actual high impedance fault (HIF) event of type double line-to-ground using real oscillography data and ATP-EMTP software. The event occured in an overhead distribution system connected to substation Salinópolis 13.8 kV, after two cabes broke and touched a soil contact surface. The reproduction method of the mentioned event is based on simple calculation of fault currents from neutral current measurements to generate the V × I curve used in the HIF model. The results show that current signals obtained from simulation match the current measurements, demonstrating the effectiveness of the proposed method.
ISSN:2472-9639