Dynamic modelling of VSC-HVDC for connection of offshore wind farms
A VSC-HVDC (Voltage Source Converter - High Voltage Direct Current) dynamic model with a set of control strategies is developed in DIgSILENT Power-Factory with the objective of analyzing the converter's operating capability for grid support during grid faults. The investigation is carried out b...
Saved in:
Main Authors: | , |
---|---|
Format: | Conference Proceeding |
Language: | English |
Subjects: | |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | A VSC-HVDC (Voltage Source Converter - High Voltage Direct Current) dynamic model with a set of control strategies is developed in DIgSILENT Power-Factory with the objective of analyzing the converter's operating capability for grid support during grid faults. The investigation is carried out based on a 165 MW offshore wind farm with induction generators and a Low Voltage Ride-Through solution of the offshore wind turbines and Static Voltage Compensator units in the point of connection with a grid represented by a reduced four-generator power grid model. VSC-HVDC promises to be a reliable alternative solution for interconnection with off-shore wind farms as they become larger, with a higher installed power capacity, increased number of wind turbines, and geographically situated at larger distances from suitable connection points in the transmission grids. (4 pages) |
---|---|