Loading…
Estimation of appropriate capacity of ventilation system based on the air infiltration rate in Korean classrooms
The appropriate capacity of a ventilation system based on the air infiltration rate in Korean classrooms is investigated to obtain optimal design conditions for ventilation systems. Theoretical and the experimental analyses are performed to estimate the proper ventilation capacity with a considerati...
Saved in:
Published in: | Journal of mechanical science and technology 2008, 22(4), , pp.788-797 |
---|---|
Main Authors: | , , , , |
Format: | Article |
Language: | English |
Subjects: | |
Citations: | Items that this one cites Items that cite this one |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | The appropriate capacity of a ventilation system based on the air infiltration rate in Korean classrooms is investigated to obtain optimal design conditions for ventilation systems. Theoretical and the experimental analyses are performed to estimate the proper ventilation capacity with a consideration of the air infiltration, the indoor air quality, and the ventilation rate. The air infiltration rate of the classroom is measured within the range of 0.5–1.5 1/h, and the required ventilation rate should be decided not by the contaminants (Formaldehyde and TVOC) emitted from the construction materials but by the carbon dioxide (CO
2
) emitted from human breath. The appropriate capacity of the ventilation system based on the air infiltration rate of the classroom for elementary schools is 500CMH and for middle and high schools is 800 CMH. The measured and the estimated values of CO
2
concentrations are very similar and the modeling equation of CO
2
concentration can be used as a reference for the proper estimation of ventilation rate in Korean schools. |
---|---|
ISSN: | 1738-494X 1976-3824 |
DOI: | 10.1007/s12206-008-0111-8 |