Loading…
Magnetization Characteristics Due to Fault Angle of Transformer Type SFCL with Two Isolated Secondary Windings
In this paper, a transformer type superconducting fault current limiter (SFCL) with two isolated secondary windings was fabricated to increase the current limiting capacity. As the magnetization current increased due to the large transient fault current immediately after the fault, the magnetization...
Saved in:
Published in: | Journal of electrical engineering & technology 2020, 15(6), , pp.2501-2508 |
---|---|
Main Authors: | , , |
Format: | Article |
Language: | English |
Subjects: | |
Citations: | Items that this one cites Items that cite this one |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | In this paper, a transformer type superconducting fault current limiter (SFCL) with two isolated secondary windings was fabricated to increase the current limiting capacity. As the magnetization current increased due to the large transient fault current immediately after the fault, the magnetization force variation, the operating range of the flux linkage, and the voltage region variation were compared at fault angles of 0° and 90°, respectively. The short-circuit test analyzed the current limiting operation, power consumption, and energy consumption characteristics according to the fault angle immediately after the fault occurrence. The results showed that the fault angle of 0° could limit the fault current much more than the fault angle of 90°. In addition, it was confirmed that the magnetization force variation, the operating range of the flux linkage, and the voltage induced in the primary winding were all much larger at the fault angle of 0° than at the fault angle of 90°. |
---|---|
ISSN: | 1975-0102 2093-7423 |
DOI: | 10.1007/s42835-020-00534-2 |