Adaptive ground fault protection schemes for turbo-generator based on third harmonic voltages
Equivalent circuits are used to study the characteristics of various generator stator ground fault protection schemes presented in the literature. The evaluation and the comparison of the characteristics of those schemes are given by means of Protection Coverage-Critical Resistance curves. Although...
Saved in:
Published in: | IEEE transactions on power delivery 1990, Vol.5 (2), p.595-603 |
---|---|
Main Authors: | , , |
Format: | Article |
Language: | English |
Subjects: | |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | Equivalent circuits are used to study the characteristics of various generator stator ground fault protection schemes presented in the literature. The evaluation and the comparison of the characteristics of those schemes are given by means of Protection Coverage-Critical Resistance curves. Although these schemes are successful in practice, they suffer disadvantage of low sensitivity which is strongly related to generator operating conditions. Two adaptive stator ground fault protection schemes based on digital techniques are developed. |
---|---|
ISSN: | 0885-8977 1937-4208 |
DOI: | 10.1109/61.53061 |