Loading…

Post arc current of vacuum interrupter after large current interruption

Postarc current characteristics of a vacuum interrupter have been examined under a condition of high-current interruption. A measurement technique was developed in which a shunt for measuring postarc current was set in a synthetic test circuit voltage source. Postarc current was measured after a 20-...

Full description

Saved in:
Bibliographic Details
Published in:IEEE transactions on power delivery 1988-10, Vol.3 (4), p.1692-1697
Main Authors: Hakamata, Y., Kurosawa, Y., Natsui, K., Hirasawa, K., Kurita, K.
Format: Article
Language:English
Subjects:
Citations: Items that this one cites
Items that cite this one
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:Postarc current characteristics of a vacuum interrupter have been examined under a condition of high-current interruption. A measurement technique was developed in which a shunt for measuring postarc current was set in a synthetic test circuit voltage source. Postarc current was measured after a 20-57 kA current interruption. The magnitude was greatly influenced by the rate of current decline. Residual resistance between electrodes was calculated from the measured values of recovery voltage and postarc current. The recovery of residual resistance was very rapid immediately after current zero and become slow later.< >
ISSN:0885-8977
1937-4208