Loading…
Post arc current of vacuum interrupter after large current interruption
Postarc current characteristics of a vacuum interrupter have been examined under a condition of high-current interruption. A measurement technique was developed in which a shunt for measuring postarc current was set in a synthetic test circuit voltage source. Postarc current was measured after a 20-...
Saved in:
Published in: | IEEE transactions on power delivery 1988-10, Vol.3 (4), p.1692-1697 |
---|---|
Main Authors: | , , , , |
Format: | Article |
Language: | English |
Subjects: | |
Citations: | Items that this one cites Items that cite this one |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | Postarc current characteristics of a vacuum interrupter have been examined under a condition of high-current interruption. A measurement technique was developed in which a shunt for measuring postarc current was set in a synthetic test circuit voltage source. Postarc current was measured after a 20-57 kA current interruption. The magnitude was greatly influenced by the rate of current decline. Residual resistance between electrodes was calculated from the measured values of recovery voltage and postarc current. The recovery of residual resistance was very rapid immediately after current zero and become slow later.< > |
---|---|
ISSN: | 0885-8977 1937-4208 |
DOI: | 10.1109/61.193973 |