Analysis of Grounding Systems Including Freely Oriented Plates of Arbitrary Shape in Multilayer Soils
This paper presents the analysis of grounding systems including freely oriented conductors and metallic plates of arbitrary shapes in horizontal multilayer soils. The analysis method yields not only the scalar potential but also the electric field and current density in the soil in the low frequency...
Saved in:
Published in: | IEEE transactions on industry applications 2015-11, Vol.51 (6), p.5189-5197 |
---|---|
Main Authors: | , , |
Format: | Article |
Language: | English |
Subjects: | |
Citations: | Items that this one cites Items that cite this one |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | This paper presents the analysis of grounding systems including freely oriented conductors and metallic plates of arbitrary shapes in horizontal multilayer soils. The analysis method yields not only the scalar potential but also the electric field and current density in the soil in the low frequency limit. Numerical results are provided for various configurations such as a single plate, a plate with rods, parallel plates, a box, or cylinders formed by multiple plates and are verified against available analytical methods. |
---|---|
ISSN: | 0093-9994 1939-9367 |
DOI: | 10.1109/TIA.2015.2448614 |