Calibration and Laboratory Testing of Computer Measuring System 8AE-PD Dedicated for Analysis of Acoustic Emission Signals Generated by Partial Discharges Within Oil Power Transformers

In the paper, there are presented a general description of the constructed measuring system 8AE-PD, the results of calibration of this system by the Hsu-Nielsen method as well as the testing of the measuring system during recording signals generated by Hsu-Nielsen sources in a steel plate and a mode...

Full description

Saved in:
Bibliographic Details
Published in:Archives of acoustics 2017-06, Vol.42 (2), p.297-311
Main Authors: Witos, Franciszek, Szerszeń, Grzegorz, Opilski, Zbigniew, Setkiewicz, Maciej, Olszewska, Aneta, Duda, Dominik, Maźniewski, Krzysztof, Szadkowski, Marek
Format: Article
Language:English
Subjects:
Citations: Items that cite this one
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:In the paper, there are presented a general description of the constructed measuring system 8AE-PD, the results of calibration of this system by the Hsu-Nielsen method as well as the testing of the measuring system during recording signals generated by Hsu-Nielsen sources in a steel plate and a modeled partial discharge (PD) source. There is also presented the methodology of investigations by the calibrated acoustic emission method. The results of analyses of PD signals coming from the modeled sources are given. In particular, there are described the properties of acoustic emission (AE) signals generated by the PDs as well as the dependencies of the peak-to-peak voltage U , the RMS voltage U and the descriptors of acronyms ADP and ADC on the apparent charge Q introduced by the modeled PD source. There are determined the limit values of the apparent charge Q introduced by the modeled PD source for which the recorded signal is identified as originating from the PDS.
ISSN:2300-262X
0137-5075
2300-262X
DOI:10.1515/aoa-2017-0032