Loading…

Experimental analysis of triple fluid vapour absorption refrigeration system driven by electrical energy and engine waste heat

In this study, performance analysis of absorption refrigeration cycle has been carried out under variable power sources namely electrical and thermal energy sources. The triple fluid vapour absorption system was used in this work. The temperatures at each point in the cycle such as generator, absorb...

Full description

Saved in:
Bibliographic Details
Published in:Thermal science 2019-01, Vol.23 (5 Part B), p.2995-3001
Main Authors: Balasubramanian, Andi, Jayaraman, Venkatesan, Sivan, Suresh, Vairavan, Mariappan
Format: Article
Language:English
Subjects:
Citations: Items that cite this one
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:In this study, performance analysis of absorption refrigeration cycle has been carried out under variable power sources namely electrical and thermal energy sources. The triple fluid vapour absorption system was used in this work. The temperatures at each point in the cycle such as generator, absorber, evaporator and condenser have been measured. The coefficient of performance of the system was calculated and then compared. The results showed that when the cycle driven by electricity, the coefficient of performance varied from 0.28-1.6 along the test time and the generator temperature changed from 66?C to 106?C. When thermal energy used to generate power, the coefficient of performance varied between 0.16 and 0.6 under the generator temperature of 98?C and 150?C. It was observed that the waste heat energy from engine exhaust can be used efficiently and can replace the conventional power source to drive the absorption refrigeration unit. nema
ISSN:0354-9836
2334-7163
DOI:10.2298/TSCI171129110A