Loading…

Passive air-conditioning of domestic using a hybrid system of solar updraft tower and a geothermal in Tikrit city-Iraq

In constructing a hybrid solar updraft tower with an underground heat exchanger, this study provides a theoretical and experimental investigation. A valuable function that lowers energy consumption in the case of domestic buildings is the Underground Tube Heat Exchanger. The submerged underground he...

Full description

Saved in:
Bibliographic Details
Published in:IOP conference series. Materials Science and Engineering 2021-02, Vol.1058 (1), p.12057
Main Authors: Abed, Fayadh M, Zaidan, Maki H, Hussein, Yousif H, Jassim, Abdullah K
Format: Article
Language:English
Subjects:
Citations: Items that this one cites
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:In constructing a hybrid solar updraft tower with an underground heat exchanger, this study provides a theoretical and experimental investigation. A valuable function that lowers energy consumption in the case of domestic buildings is the Underground Tube Heat Exchanger. The submerged underground heat exchanger tube for heating in winter season and cooling in summer and the air is to be supplied by the influence of solar updraft tower to the building. The findings show that at 3 m depth from the earth, which is called buried depth at a 152 mm outer diameter, the maximum efficiency of the underground heat exchanger system. In comparison, with rising velocity of air, the temperature of the outlet air from the ground heat exchanger increases, varying from (22.2- 28 °C) and also increases with increasing pipe diameter and decreases with increasing tube length. The difference between the findings of the theoretical and the experimental tests was 1.8 %. The combined geothermal heat exchanger and solar updraft tower system is used as an air conditioning system and was satisfactory efficient for thermal building loads.
ISSN:1757-8981
1757-899X
DOI:10.1088/1757-899X/1058/1/012057