Research on effect of lightning shielding level of EHVDC transmission line by installing coupling ground wire
Lightning shielding failure is the main reason causing lightning flashover of Jiangcheng EHVDC transmission line because of the designed ground wire protection angle. Based on the electric-geometry model, a simulation model including the coupling ground wire is established by using MATLAB. The effec...
Saved in:
Published in: | IOP conference series. Earth and environmental science 2019-08, Vol.310 (3), p.32058 |
---|---|
Main Authors: | , , , |
Format: | Article |
Language: | English |
Subjects: | |
Citations: | Items that this one cites |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | Lightning shielding failure is the main reason causing lightning flashover of Jiangcheng EHVDC transmission line because of the designed ground wire protection angle. Based on the electric-geometry model, a simulation model including the coupling ground wire is established by using MATLAB. The effect of the coupling ground wire at different height and horizontal position on lightning shielding failure flashover rate is analysed. Results show that coupling ground wire can reduce the lightning shielding failure flashover rate and the lightning shielding performance increases with the increase of the height of the wire and the horizontal distance between the axis of the tower and the coupling ground wire. |
---|---|
ISSN: | 1755-1307 1755-1315 |
DOI: | 10.1088/1755-1315/310/3/032058 |