Analysis of Harmonic Effect of Photovoltaic Integration into Medium Power System

Renewable Energy is starting to grow rapidly, the use of solar energy in Indonesia has a good development. According to the grid code issued by the national utility company, the maximum standard harmonic limit is 5%. Harmonic is mostly caused by non-linear loads that form a distorted sine wave, whic...

Full description

Saved in:
Bibliographic Details
Published in:IOP conference series. Earth and environmental science 2019-10, Vol.353 (1), p.12002
Main Authors: Apriansyah, M E, Ramadhan, U F, Aryani, D R, Utomo, A R
Format: Article
Language:English
Subjects:
Citations: Items that this one cites
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:Renewable Energy is starting to grow rapidly, the use of solar energy in Indonesia has a good development. According to the grid code issued by the national utility company, the maximum standard harmonic limit is 5%. Harmonic is mostly caused by non-linear loads that form a distorted sine wave, which leads the equipment to become hotter faster, adding losses and reducing the equipment lifetime. The simulation method uses ETAP software to obtain values from Total Harmonic Distortion (THD) on the 20kV and 150 kV Beta substations sides with several scenario simulations of photovoltaic power plant integration with a capacity from 5 to 20 MWp with multiple of 5. The simulation results have shown that the maximum THDv value in the scenario at 20 kV Beta substation is 0.26% and at 150kV Beta substation is 0.1%. This value is still below the standard limit, so by the integration of PV plant, system still operates securely.
ISSN:1755-1307
1755-1315
DOI:10.1088/1755-1315/353/1/012002