Loading…
An Analytical Approach to Locate Short Circuit Fault in a Cable Using Sweep Frequency Response Analysis
In this article, analytical methods are proposed for the location of a short circuit fault in a power cable using sweep frequency response analysis (SFRA). The impedance spectroscopy is estimated using classical transmission line theory, whereas the driving point impedance function of the cable is p...
Saved in:
Published in: | IEEE transactions on industrial electronics (1982) 2023-05, Vol.70 (5), p.5235-5244 |
---|---|
Main Authors: | , |
Format: | Article |
Language: | English |
Subjects: | |
Citations: | Items that this one cites Items that cite this one |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | In this article, analytical methods are proposed for the location of a short circuit fault in a power cable using sweep frequency response analysis (SFRA). The impedance spectroscopy is estimated using classical transmission line theory, whereas the driving point impedance function of the cable is proposed to be constructed either by using experimental SFRA data or analytically from the knowledge of the frequency-dependent parameters, material properties, and dimensions of the cable. Finally, an analytical formula is proposed for the estimation of the location of a short-circuit fault using the location of poles and zeros of the impedance function before and after the fault. The formulae are validated using finite element method (FEM) software simulations as well as experimentally on a test cable. |
---|---|
ISSN: | 0278-0046 1557-9948 |
DOI: | 10.1109/TIE.2022.3189080 |