Loading…

Quantifying Peak Load-Carrying Capability: A Comprehensive Reliability Analysis of Grid-Connected Hybrid Systems

Energy leaders around the world are constantly looking into feasibility and opportunities in renewable energy to diversify their energy sources. This study examines the reliability of a grid-connected microgrid consisting of solar energy, wind energy, and storage batteries to supply the required loa...

Full description

Saved in:
Bibliographic Details
Published in:Sustainability 2024-11, Vol.16 (22), p.10107
Main Authors: Almgbel, Osamah H, Seedahmed, Mustafa M. A, Alhussainy, Abdullah Ali, Alghamdi, Sultan, Rawa, Muhyaddin, Alturki, Yusuf A
Format: Article
Language:English
Subjects:
Citations: Items that this one cites
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:Energy leaders around the world are constantly looking into feasibility and opportunities in renewable energy to diversify their energy sources. This study examines the reliability of a grid-connected microgrid consisting of solar energy, wind energy, and storage batteries to supply the required load and share the surplus with the grid. As the reliability of each component separately has an impact on system reliability, in this study, the loss of load expectation (LOLE) technique was used to estimate the peak load-carrying capability (PLCC) of the systems and the duration of outages as a means of analyzing the reliability of these systems and selecting the optimal combination among the cases. Moreover, this study used the load data of the area under study as the primary load and considered the grid as a secondary load to share the surplus after fulfilling the demand requirements. Furthermore, ten cases of grid-connected system configurations were considered to conduct this research, incorporating various combinations of solar panels, wind turbines (WTs), and batteries. The results revealed that, while maintaining an acceptable risk level represented by an LOLE of 0.1 days per year, the WT (850 MW) case emerged as the leading power producer compared to the other cases. It was able to produce 840.245 MW and 818.345 MW as the total power produced and the amount of surplus power that will be delivered to the grid after meeting the primary load needs in the area under study, respectively. This analysis can be informative for administrators in charge of planning and policy-making, helping them to take appropriate action.
ISSN:2071-1050
2071-1050
DOI:10.3390/su162210107