Apparatus for Online Power Transformer Winding Monitoring Using Bushing Tap Injection

Online transformer condition monitoring techniques based on transfer function methods, such as transmission-line diagnostics and swept frequency-response analysis, require the injection of a known test signal into the transformer. On larger power transformers, a practical method is to use the availa...

Full description

Saved in:
Bibliographic Details
Published in:IEEE transactions on power delivery 2009-07, Vol.24 (3), p.996-1003
Main Authors: De Rybel, T., Singh, A., Vandermaar, J.A., Wang, M., Marti, J.R., Srivastava, K.D.
Format: Article
Language:English
Subjects:
Citations: Items that this one cites
Items that cite this one
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:Online transformer condition monitoring techniques based on transfer function methods, such as transmission-line diagnostics and swept frequency-response analysis, require the injection of a known test signal into the transformer. On larger power transformers, a practical method is to use the available bushing tap connection. In this paper, we will discuss a custom high-power signal generator that injects high-frequency signals on the bushing tap of the transformer under investigation, as well as a circuit to replace the bushing tap short and allow online operation of the system. Finally, the system is demonstrated on a 650 kV transformer.