Apparatus for Online Power Transformer Winding Monitoring Using Bushing Tap Injection
Online transformer condition monitoring techniques based on transfer function methods, such as transmission-line diagnostics and swept frequency-response analysis, require the injection of a known test signal into the transformer. On larger power transformers, a practical method is to use the availa...
Saved in:
Published in: | IEEE transactions on power delivery 2009-07, Vol.24 (3), p.996-1003 |
---|---|
Main Authors: | , , , , , |
Format: | Article |
Language: | English |
Subjects: | |
Citations: | Items that this one cites Items that cite this one |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | Online transformer condition monitoring techniques based on transfer function methods, such as transmission-line diagnostics and swept frequency-response analysis, require the injection of a known test signal into the transformer. On larger power transformers, a practical method is to use the available bushing tap connection. In this paper, we will discuss a custom high-power signal generator that injects high-frequency signals on the bushing tap of the transformer under investigation, as well as a circuit to replace the bushing tap short and allow online operation of the system. Finally, the system is demonstrated on a 650 kV transformer. |
---|---|