Algorithm to Evaluate Substation Reliability With Cut and Path Sets

An algorithm is presented to evaluate substation reliability. This algorithm takes into account breaker failures, blocked breakers, and breaker backup protection to isolate faults in a substation. Passive and active outages are considered. Two evaluation criteria are used: substation fails if one po...

Full description

Saved in:
Bibliographic Details
Published in:IEEE transactions on industry applications 2008-11, Vol.44 (6), p.1851-1858
Main Authors: Vega, M., Sarmiento, H.G.
Format: Article
Language:English
Subjects:
Citations: Items that this one cites
Items that cite this one
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:An algorithm is presented to evaluate substation reliability. This algorithm takes into account breaker failures, blocked breakers, and breaker backup protection to isolate faults in a substation. Passive and active outages are considered. Two evaluation criteria are used: substation fails if one point of load fails, and substation fails if all points of load fail. The cost of energy not supplied is used to evaluate and economically compare the substation reliability.