Design of Wide-Area Damping Controllers for Interarea Oscillations

This paper develops a systematic procedure of designing a centralized damping control system for power grid interarea oscillations putting emphasis on the signal selection and control system structure assignment. Geometric measures of controllability/observability are used to select the most effecti...

Full description

Saved in:
Bibliographic Details
Published in:IEEE transactions on power systems 2008-08, Vol.23 (3), p.1136-1143
Main Authors: Yang Zhang, Bose, A.
Format: Article
Language:English
Subjects:
Citations: Items that this one cites
Items that cite this one
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:This paper develops a systematic procedure of designing a centralized damping control system for power grid interarea oscillations putting emphasis on the signal selection and control system structure assignment. Geometric measures of controllability/observability are used to select the most effective stabilizing signals and control locations. Line power flows and currents are found to be the most effective input signals. The synthesis of the controller is defined as a problem of mixed H 2 / H infin output-feedback control with regional pole placement and is resolved by the linear matrix inequality (LMI) approach. A tuning process and nonlinear simulations are then used to modify the controller parameters to ensure the performance and robustness of the controller designed with linear techniques. The design process is tested on the New England 39-bus ten-machine system.
ISSN:0885-8950
1558-0679
DOI:10.1109/TPWRS.2008.926718