Loading…

HTS Transformer: Construction Details, Test Results, and Noted Failure Mechanisms

An experimental high temperature superconducting transformer has been designed and built using Bi2223 HTS tape. The transformer is unique in that the magnetic circuit is comprised of air and a silicon steel partial core. Electrical tests were performed on the transformer and it was found to be 98.6%...

Full description

Saved in:
Bibliographic Details
Published in:IEEE transactions on power delivery 2011-01, Vol.26 (1), p.394-399
Main Authors: Lapthorn, A C, Chew, I, Enright, W G, Bodger, P S
Format: Article
Language:English
Subjects:
Citations: Items that this one cites
Items that cite this one
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:An experimental high temperature superconducting transformer has been designed and built using Bi2223 HTS tape. The transformer is unique in that the magnetic circuit is comprised of air and a silicon steel partial core. Electrical tests were performed on the transformer and it was found to be 98.6% efficient at full load. The transformer failed during a full load endurance run and an investigation was carried out to determine the cause of the failure. The cause was believed to be from operating the HTS windings close to critical conditions. Presentation of the failure details will be of use to other researchers who are building HTS transformers.
ISSN:0885-8977
1937-4208
DOI:10.1109/TPWRD.2010.2061874