A comparison of magnetic fields inside and outside high-voltage urban 110-kV power substations with the exposure recommendations of the Ukrainian regulatory authorities
The aim of this study was to carry out theoretical investigations of power frequency magnetic fields (MFs), produced inside and outside the domain of urban 110-kV power substations and to establish a correspondence between the levels of the fields and the specified population limits as defined by Uk...
Saved in:
Published in: | Radiation protection dosimetry 2013-05, Vol.154 (4), p.417-429 |
---|---|
Main Authors: | , , |
Format: | Article |
Language: | English |
Subjects: | |
Citations: | Items that this one cites |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | The aim of this study was to carry out theoretical investigations of power frequency magnetic fields (MFs), produced inside and outside the domain of urban 110-kV power substations and to establish a correspondence between the levels of the fields and the specified population limits as defined by Ukrainian regulations. The fields produced by high-voltage substations were studied based on the application of the numerical finite element methodology. The investigations have shown that magnetic flux density values calculated inside and outside the considered 110-kV power substations do not reach the exposure limits specified by the Ukrainian regulations (1750 μT) and by international guidelines (ICNIRP 2010). Inside the domain of the substation, the maximum value of MFs was found under the 10-kV busbars and it equalled 420 μT. |
---|---|
ISSN: | 0144-8420 1742-3406 |
DOI: | 10.1093/rpd/ncs268 |