Early detection of fires in electrical installations by thermally modulated SnO2/additive-multi sensor arrays
In this work, a setup for generation and analysis of pyrolysis gases, which can operate multi gas sensor arrays of different SnO2/Additive admixtures, is introduced. The gas sensor arrays are thermo-cyclically operated and are investigated towards their characteristic features of the resulting condu...
Saved in:
Published in: | Sensors and actuators. B, Chemical Chemical, 2015-10, Vol.217, p.36-40 |
---|---|
Main Authors: | , , |
Format: | Article |
Language: | English |
Subjects: | |
Citations: | Items that this one cites Items that cite this one |
Online Access: | Get full text |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | In this work, a setup for generation and analysis of pyrolysis gases, which can operate multi gas sensor arrays of different SnO2/Additive admixtures, is introduced. The gas sensor arrays are thermo-cyclically operated and are investigated towards their characteristic features of the resulting conductance-over-time profiles (CTPs) for identification and analysis of pyrolysis gases at low concentrations emitted for instance by overloaded electrical cables. Several SnO2/Additive gas sensitive layers have been examined with pyrolysis gas related model gases like CO, methane and propene and were tested on their stability, sensitivity and characteristic CTP-features when exposed to pyrolysis gases of PVC insulation materials. |
---|---|
ISSN: | 0925-4005 1873-3077 |
DOI: | 10.1016/j.snb.2015.02.014 |